The Fuse Cutout type OEI was developed to operate in overhead distribution systems rated at 11
kV to 38 kV grounded systems with 100 or 200 A nominal currents.
Especially designed to protect transformers, capacitors, cables or lines.
It is robust construction, made of rigorously tested material, will interrupt all faults under the
most severe conditions, maintaining mechanical and electric characteristics.
The inserts, hardware and structural bolts and nuts are made from heavy galvanized steel.
The Fuse Cutout type OEI can be applied on all three-phase system rated at or below the maximum
operational rating of the cutout.
Performance Characteristic |
Applied standard | IEEE C37.42-2009 |
Catalog number |
|
Nominal system voltage kV | 33 |
Rated Frequency Hz | 50 |
Rated m aximum(design) voltage | 38 |
Rated Continuous current A-RMS | 100 |
Rated Interrupting current asymmetrical/symmetrical A-RMS | 8000/5000 |
BIL 1.2x50 µs kV-peak | 150 |
Minimum critical impulse flashover voltage(CFO)KV peak | 165 |
Dry withstand voltage kV-RMS | 70 |
Wet withstand voltage kV-RMS | 60 |
Creepage distance to group Min.mm | 650 |
Minimum creepage factor of insulator (Creepage Distance/arcing distance) | 2.3 |
HIGH VOLTAGE EXPULSION TYPE FUSE LINKS
TABLE OF CONTENTS
ITEM TITLE PAGE
PART 1 GENERAL
1.01 SCOPE E13 1
1.02 STANDARDS E13 1
1.03 SERVICE CONDITIONS E13 2
1.04 SYSTEM CONDITIONS E13 2
1.05 TESTING E13 2
1.06 SPARES E13 3
1.07 PACKING AND SHIPMENT E13 3
1.08 SUBMITTALS E13 3
PART 2 PRODUCTS
2.01 DESIGN E13 4
A. Standardization of Fuse Links E13 4
B. Rating of Fuse Links E13 4
C. Characteristics of Fuse Links E13 4
2.02 MATERIALS E13 4
A. Current Carrying Parts of Fuse Links E13 4
B. Fuse Link Button E13 5
C. Length of Fuse Links E13 5
D. Pull on Fuse Links E13 5
E. Identification E13 5
TECHNICAL DATA SCHEDULE E13 6
PART 1 GENERAL
1.01 SCOPE
This Specification covers the design, manufacturing, testing, supply, delivery and performance requirements of HV Expulsion Type Fuse Links for use by the Electricity Company of Ghana Limited.
1.02 STANDARDS
The fuse links shall comply with the latest editions of and amendments to, the standards/specifications listed below:
IEC - International Electrotechnical Commission
IEC 60282 - High Voltage Fuses Part 2: Expulsion and similar fuses
ANSI American National Standards Institute
IEEE C37.41 - Design for High Voltage Fuses, Distribution Enclosed Single Pole Air Switches. Fuse Disconnecting Switches and Accessories.
ANSI C37.42 - American National Standard Specifications for Distribution Cutouts and Fuse Links.
NEMA National Electrical Manufacturers Association
NEMA SG2 - High Voltage Fuses
1.03 SERVICE CONDITIONS
As in Specification H 0C
1.04 SYSTEM CONDITIONS
As in Specification H 0C
1.05 TESTING
Type Tests
A. The Supplier shall confirm on the attached schedule that the following tests have been performed according to ANSI C37.42.
1. Melting Current Tests; Table 6
2. Temperature Rise Tests
3. Time/Current Characteristic Tests
B. Type/Design Tests may (at the Purchaser's discretion) be dispensed with if the Supplier/Contractor furnishes evidence to the Purchaser's satisfaction that the relevant tests have already been performed on identical equipment. In this case the Supplier shall provide documentary proof in the form of Certified Test Certificates that the assembled equipment and its component parts been successfully typetested by an independent testing authority in accordance with the relevant clauses of referenced Standards. Test Certificates as evidence of successful completion of type tests shall be submitted as part of the Bid.
C. Inspection
The Purchaser reserves the right to witness the manufacturing process, any type tests specifically performed on the materials to be supplied to Customer and any routine tests required in the manufacture and supply of such equipment. The Supplier shall provide free access to the Purchaser to any site where such manufacturing process, or tests, either type or routine tests are taking place. The Supplier shall bear the in plant costs of such witness. The Supplier shall provide the Purchaser of a schedule of manufacture and tests at least two weeks before the events are to occur.
1.06 SPARES
(NOT APPLICABLE)
1.07 PACKING AND SHIPMENT
As in Specification H 0C
1.08 SUBMITTALS
As in Specification H 0C
PART 2 PRODUCTS
2.01 DESIGN
A. Standardization of Fuse Links (Mechanical/Interchangeable).
High voltage expulsion fuses shall be suitable for use on the Expulsion fusegears described in the associated specifications H 16 and H 34.
B. Rating of Fuse Links
The preferred rating of fuse links shall be 3A, 5A, 8A, 16A, 25A, 40A, 63A and 100A at 11kV and 1A, 2A, 3A, 5A, 8A, 16A, 20A and 31.5A at 33kV. The rated current of the fuse link is the maximum current which it will carry continuously without deterioration and undue heating. Supplier shall state on the attached schedule the maximum temperature in oC attained by the fuse link after continuous operation at maximum rating.
C. Performance Characteristics of Fuse Links
1. The fuse links are required to give protection against short circuits. They shall be so rated and shall have such blowing characteristics as to be suitable for selective operations with the fuse links at present in use on the system namely Type K i.e. fast, fuse links to NEMA SG2 and ANSI C37.42 1981.
2. The Supplier shall present to the Purchaser timecurrent characteristics of all the distribution fuselinks on offer. The performance characteristics of the fuselinks shall include:
(a) Meltingtimecurrent characteristics
(b) Total clearingtimecurrent
The timecurrent characteristics shall be presented as curves.
The Supplier shall state the minimum and maximum melting currents required to melt the fuse links at the three appropriate time points used in Table 6 {meltingcurrents for TypeK (fast) fuse links) of ANSI C37.42 1981
2.02 MATERIALS
A. Current carrying Parts of Fuse Links
All current carrying parts of the fuse links shall be nonferrous material; the main requirements being resistance to atmospheric corrosion. Tin is not acceptable as a possible element.
Supplier shall state composition of:
1. Fuse Element
2. Fuse Link
B. Fuse Link Button
The diameter of the button head cap on fuse links shall be 19.1mm. Removable type button heads are preferred for use with 11kV fusegear.
C. Length of Fuse Links
The minimum overall length of fuse links rated 1 to 100 amperes shall be:
: 510mm for 11kV units per ANSI C.37.42
: 762mm for 33kV units per ANSI C.37.42
D. Pull on Fuse Links (Tensile Withstand Strength)
The expulsion fusegear shall operate satisfactorily while exerting a pull of 44.5N on the fuse link per ANSI C.37.42, 3.2.3.4 1981.
E. Identification
Each fuse link must have stamped on it:
1. Manufacturers name or identifying mark
2. Continuous current rating
3. Type designation, K or T
SPECIFICATION H 13
HIGH VOLTAGE EXPULSION TYPE FUSE LINKS
TECHNICAL DATA SCHEDULE
Item Description Unit Purchaser's Supplier's
Requirements Offer
1. Standard specification with which See Clause
fuse link shall comply and be tested. 1.02 __________
2. Are Type test certificates according
to Clause 1.05? Yes __________
3. Are type test certificates, quality
control procedures, and users
list included with tender? Yes __________
4. Can fuse links be used in any make
of IEC standard Fusegear? Yes __________
5. Rated current of fuse 3, 5, 8, 16, 25, 40
links 63 and 100 at 11kV,
1, 2, 3, 5, 8, 16 __________
20, 31.5A at 33kV. __________
6. Maximum Temperature in oC
attained by the Fuse Link after
continuous operation at maximum
rating with maximum ambient
temperature of 40oC. oC __________
7. Type of Fuse links? __________
Fusing current tolerance Melting
current (300, 10, 0.1, sec) sec __________
8. Composition of
1. Fuse element (Tin not acceptable) __________
2. fuse link __________
9. Diameter of fuse link
button and type mm 19.1 __________
10. Length of fuse links for: 11kV isolators mm 510 __________ 33kV isolators mm 762 __________ 11. Tensile withstand strength of fuse links N 44.5 __________ 12. Are fuse links stamped according to Clause 2.02 E? Yes __________ SIGNED: __________________________________ COMPANY: _________________________________ POSITION IN COMPANY: _________________________________ Date: _____________________ _______________________ COMPANY STAMP