Product Description

 The Fuse Cutout type OEI was developed to operate in overhead distribution systems rated at 11
kV to 38 kV grounded systems with 100 or 200 A nominal currents.
Especially designed to protect transformers, capacitors, cables or lines.
It is robust construction, made of rigorously tested material, will interrupt all faults under the
most severe conditions, maintaining mechanical and electric characteristics.
The inserts, hardware and structural bolts and nuts are made from heavy galvanized steel.
The Fuse Cutout type OEI can be applied on all three-phase system rated at or below the maximum
operational rating of the cutout.
 
Performance Characteristic
Applied standard IEEE C37.42-2009
Catalog number
Nominal system voltage kV 33
Rated Frequency Hz 50
Rated m aximum(design) voltage 38
Rated Continuous current A-RMS 100
Rated Interrupting current asymmetrical/symmetrical A-RMS 8000/5000
BIL 1.2x50 µs kV-peak 150
Minimum critical impulse flashover voltage(CFO)KV peak 165
Dry withstand voltage kV-RMS 70
Wet withstand voltage kV-RMS 60
Creepage distance to group Min.mm 650
Minimum creepage factor of insulator (Creepage Distance/arcing distance) 2.3
HIGH VOLTAGE EXPULSION TYPE FUSE LINKS
 
                                           TABLE OF CONTENTS
 
ITEM                                                                                                                           TITLE                                              PAGE
 
PART 1 GENERAL
 
1.01                                                                                                                             SCOPE                                                    E13 1
 
1.02                                                                                                                             STANDARDS                                                E13 1
 
1.03                                                                                                                             SERVICE CONDITIONS                                           E13 2
 
1.04                                                                                                                             SYSTEM CONDITIONS                                     E13 2
 
1.05                                                                                                                             TESTING                                                       E13 2
 
1.06                                                                                                                             SPARES                                                         E13 3
 
1.07                                                                                                                             PACKING AND SHIPMENT                                    E13 3
 
1.08                                                                                                                             SUBMITTALS                                               E13 3
 
PART 2 PRODUCTS
 
2.01                                                                                                                             DESIGN                                                         E13 4
 
A.                                                                                                                    Standardization of Fuse Links                        E13 4
B.                                                                                                                    Rating of Fuse Links                                      E13 4
C.                                                                                                                    Characteristics of Fuse Links                                 E13 4
 
2.02                                                                                                                             MATERIALS                                                        E13 4
 
A.                                                                                                                    Current Carrying Parts of Fuse Links                                  E13 4
B.                                                                                                                    Fuse Link Button                                     E13 5
C.                                                                                                                    Length of Fuse Links                                      E13 5
D.                                                                                                                    Pull on Fuse Links                                          E13 5
E.                                                                                                                     Identification                                                  E13 5
 
TECHNICAL DATA SCHEDULE                                                                                           E13 6

PART 1           GENERAL
 
1.01       SCOPE
 
This Specification covers the design, manufacturing, testing, supply, delivery and performance requirements of HV Expulsion Type Fuse Links for use by the Electricity Company of Ghana Limited.
 
1.02     STANDARDS
 
The fuse links shall comply with the latest editions of and amendments to, the standards/specifications listed below:
 
IEC                                                   -      International Electrotechnical Commission
 
IEC 60282                                 -      High Voltage Fuses Part 2: Expulsion and similar fuses
 
ANSI                                                      American National Standards Institute
 
IEEE C37.41                             -      Design for High Voltage Fuses, Distribution Enclosed Single Pole Air Switches.  Fuse Disconnecting Switches and Accessories.
 
ANSI C37.42                             -      American National Standard Specifications for Distribution Cutouts and Fuse Links.
 
NEMA                                                    National Electrical Manufacturers Association
 
NEMA SG2                               -      High Voltage Fuses

 
 
1.03     SERVICE CONDITIONS
 
As in Specification H 0C
 
 
1.04     SYSTEM CONDITIONS
 
As in Specification H 0C
 
 
1.05     TESTING
 
Type Tests
 
A.        The Supplier shall confirm on the attached schedule that the following tests have been performed according to ANSI C37.42.
 
1.         Melting Current Tests; Table 6
 
2.         Temperature Rise Tests
 
3.         Time/Current Characteristic Tests
 
B.        Type/Design Tests may (at the Purchaser's discretion) be dispensed with if the Supplier/Contractor furnishes evidence to the Purchaser's satisfaction that the relevant tests have already been performed on identical equipment.  In this case the Supplier shall provide documentary proof in the form of Certified Test Certificates that the assembled equipment and its component parts been successfully typetested by an independent testing authority in accordance with the relevant clauses of referenced Standards.  Test Certificates as evidence of successful completion of type tests shall be submitted as part of the Bid.
 
C.        Inspection
 

The Purchaser reserves the right to witness the manufacturing process, any type tests specifically performed on the materials to be supplied to Customer  and any routine tests required in the manufacture and supply of such equipment.  The Supplier shall provide free access to the Purchaser to any site where such manufacturing process, or  tests, either type or routine tests are taking place.  The Supplier shall bear the in plant costs of such witness.  The Supplier shall provide the Purchaser of a schedule of manufacture and tests at least two weeks before the events are to occur.
 
 
1.06     SPARES
 
(NOT APPLICABLE)
 
 
1.07     PACKING AND SHIPMENT
 
As in Specification H 0C
        
 
1.08     SUBMITTALS
 
As in Specification H 0C

PART 2           PRODUCTS
 
2.01     DESIGN
 
A.        Standardization of Fuse Links (Mechanical/Interchangeable).
 
High voltage expulsion fuses shall be suitable for use on the Expulsion fusegears described in the associated specifications H 16 and H 34.
 
B.        Rating of Fuse Links
 
The preferred rating of fuse links shall be 3A, 5A, 8A, 16A, 25A, 40A, 63A and 100A at 11kV and 1A, 2A, 3A, 5A, 8A, 16A, 20A and 31.5A at 33kV.  The rated current of the fuse link is the maximum current which it will carry continuously without deterioration and undue heating.  Supplier shall state on the attached schedule the maximum temperature in oC attained by the fuse link after continuous operation at maximum rating.
 
C.        Performance Characteristics of Fuse Links
 
1.         The fuse links are required to give protection against short circuits.  They shall be so rated and shall have such blowing characteristics as to be suitable for selective operations with the fuse links at present in use on the system namely Type K i.e. fast, fuse links to NEMA SG2 and ANSI C37.42 1981.
 
2.         The Supplier shall present to the Purchaser timecurrent characteristics of all the distribution fuselinks on offer.  The performance characteristics of the fuselinks shall include:
 
(a)        Meltingtimecurrent characteristics
(b)        Total clearingtimecurrent
 
The timecurrent characteristics shall be presented as curves.
 
The Supplier shall state the minimum and maximum melting currents required to melt the fuse links at the three appropriate time points used in Table 6 {meltingcurrents for TypeK (fast) fuse links) of ANSI C37.42 1981
 
 
2.02       MATERIALS
 
A.        Current carrying Parts of Fuse Links
 
All current carrying parts of the fuse links shall be nonferrous material; the main requirements being resistance to atmospheric corrosion.  Tin is not acceptable as a possible element.
 

Supplier shall state composition of:
 
1.         Fuse Element
 
2.         Fuse Link
 
B.        Fuse Link Button
 
The diameter of the button head cap on fuse links shall be 19.1mm.  Removable type button heads are preferred for use with 11kV fusegear.
 
C.        Length of Fuse Links
 
The minimum overall length of fuse links rated 1 to 100 amperes shall be:
 
:           510mm for 11kV units per ANSI C.37.42
 
:           762mm for 33kV units per ANSI C.37.42
 
D.        Pull on Fuse Links (Tensile Withstand Strength)
 
The expulsion fusegear shall operate satisfactorily while exerting a pull of 44.5N on the fuse link per ANSI C.37.42, 3.2.3.4 1981.
 
E.         Identification
 
Each fuse link must have stamped on it:
 
1.         Manufacturers name or identifying mark
 
2.         Continuous current rating
 
3.         Type designation, K or T
 
 
 
 
 
 
 
 
 
 
 
 
 

                                                          SPECIFICATION H 13
 
                                 HIGH VOLTAGE EXPULSION TYPE FUSE LINKS
 
                                                 TECHNICAL DATA SCHEDULE
 
Item                                                                                                                              Description                 Unit       Purchaser's          Supplier's
Requirements               Offer
 
1.                                                                                                                                 Standard specification with which               See Clause          
                                                                                            fuse link shall comply and be tested.                     1.02                __________
 
2.                                                                                             Are Type test certificates according              
to Clause 1.05?                                                                                                                     Yes        __________
 
3.         Are type test certificates, quality
control procedures, and users                                                    
list included with tender?                                                                                              Yes        __________
 
4.         Can fuse links be used in any make
of IEC standard Fusegear?                                                                                            Yes        __________
       
5.                                                                                             Rated current of fuse                                  3, 5, 8, 16, 25, 40
links                                                                                                                  63 and 100 at 11kV,
1, 2, 3, 5, 8, 16           __________
20, 31.5A at 33kV.      __________
                                    
6.         Maximum Temperature in oC
attained by the Fuse Link after
continuous operation at maximum     
rating with maximum ambient
temperature of 40oC.                                                                                               oC                        __________
 
7.         Type of Fuse links?                                                       __________
                                                                                                                              Fusing current tolerance Melting                                   
current (300, 10, 0.1, sec)                                                                                sec                       __________
       
8.         Composition of
                                                                                                                              1. Fuse element (Tin not acceptable)                                __________
2. fuse link                                                                                                                                                 __________
 
9.         Diameter of fuse link
button and type                                                                                                       mm        19.1              __________
 
 
 

10.       Length of fuse links for:
11kV isolators                                                                                                                mm        510        __________
33kV isolators                                                                                                                mm        762        __________
 
11.       Tensile withstand strength of
fuse links                                                                                                   N           44.5                  __________
             
 
12.       Are fuse links stamped
according to Clause 2.02 E?                                                                                          Yes        __________
          
 
SIGNED:                 __________________________________
 
COMPANY:                _________________________________
 
POSITION IN COMPANY:    _________________________________
 
Date:   _____________________                                  _______________________
COMPANY STAMP
Previous: 
Next: 
ORIENT ELECTRIC
OEI is able to lead turn-key projects and also cooperate in specific parts of engineering projects.

Contact Us

Tel : 0722-7523677
Fax: 0722-7523818
Email: orientbest@yahoo.com
sales@oeipower.com
QQ: 280966439
WhatsApp:008618837710360
Wechat:
 18837710360
Add: No.8  Yingshan Industrial Park,Yingshan Avenue,Guangshui City,
Hubei Province,China 432799
Copyright © Orient Electric International Group Limited.